Phase: Single phase with ground

Capacity:6000VA/ 5400W

INPUT

Nominal voltage: 220 – 240Vac

Input voltage range: 110~286Vac

Frequency range: 40~70Hz (50/60Hz Auto-Sensing)

Power factor: ≥0.99

Bypass voltage range: Max.voltage:230~264Vac

Min.voltage:176~220Vac

OUTPUT

Output voltage: 208/220/230/240Vac

Power factor: 0.9

Output frequency: Line Mode: ±10% of the rated frequency

Bat. Mode: (50/60±0.1%)Hz

Crest factor: 3:1

Harmonic distortion (THDv); ≤2% Linear load

≤5% Non linear load

Transfer time: AC mode to Bat.Mode: 0ms

Inverter to Bypass: 5ms (Typical)

Output waveform: Pure Sinewave

Overload: Line Mode: Load≤105% long time running; ≤125% last 10min; ≤130% last 30s; >130% turn to bypass mode                                immediately

Bypass Mode: 40A (Breaker)

Efficiency: 93.5%

BATTERY

Battery voltage: 240Vdc (Adjustable) ,without neutral

Capacity (Standard unit): 9Ah/12V

Typical recharging time: 6~8 hours (to 90% of full capacity)

Charging current: 1A (Standard unit); Long run unit Max.current 8A (Charging current can be set according to battery capacity)

INDICATORS

LED display: Line mode, Bat.mode, ECO mode, Bypass mode, Battery low voltage, Overload & UPS fault

LCD display: Input voltage,Input frequency,Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature& Remaining battery backup time.

PHYSICAL

Dimension W x D×H (mm): H:191 x 460 x 337;S:191 x 460 x 720 (With wheel)

MECER 6KVA – 10KVA ONLINE UPS DATASHEET